DC Current Sensor
AC Current Sensor
Measuring Instruments
What is parasitic current ? Let's try to measure by M-730 !!
method of operation
SPECIFICATIONS | |
---|---|
Withstanding Voltage | AC 3700V/1 minute between CT and outer case |
Storage Temperature | -10~60℃, < 70%RH (without condensation) |
Accuracy | DC Current (Accuracy:23℃±5℃, less than 85%RH) Range/Measuring Range/Resolution/Accuracy 100mA/0.1~±99.99mA/0.01mA/±1%rdg±10dgtt 1000mA/1~±300mA/0.1mA/±1%rdg±10dgt 1000mA/±300.1~±700mA/0.1mA/±2%rdg±10dgt 1000mA/±700.1~±999.9mA/0.1mA/±3%rdg±10dgt Influence of terrestrial magnetism : Less than ±2.0mA Influence of magnetization : Less than ±2.0mA by DC 1.5A on/off Influence of CT opening and closing: Less than ±1.0mA Max. input current : DC 1.5A AC Current (Accuracy:23℃±5℃, less than 85%RH) Range/Measuring Range/Resolution/Accuracy 100mA/0~99.99mA/0.01mA/±2%rdg±10dgt(50/60Hz) 1000mA/0~999.9mA/0.1mA/±2%rdg±10dgt(50/60Hz) 10A/0~9.999A/0.001A/±1%rdg±10dgt(50/60Hz) Max. input current : AC 20A |
Operating Temperature | 0~50℃, < 85%RH (without condensation) |
Power supply | LR6, AM-3 or AA size battery×4 |
Dimension | Main unit:78(W)×155(H)×32(D)mm, Approx. 280g 33(W)×170(H)×24(D)mm CT (CTP-30DC):1.2m lead, Approx. 165g |
AC Conversion | Average sensing rms reading |
Safety standard | IEC61010-1, IEC61010-2-032 CATⅡ 600V or CATⅢ 300V |
Jaw opening capability | 30mmφ |
Limitation of circuit voltage | Less than AC/DC 600V |
Accessories | Carrying case, Batteries, Instruction manual |
Current Consumption | Approx. 9mA (Approx. 200 hours continuous) |
Option | Cable for recorder |
Sampling rate | 1 time/sec. for DC and 6 times/sec. for AC |
Display | Max. 2000 count on LCD with annunciators |
Measuring function | AC/DC leakage current |
Measuring ranges | DC 100mA/1000mA, AC 100mA/1000mA/10A (45Hz-65Hz) |
A/D Conversion | Dual slope integration method |
Over range indication | "OL" mark on LCD |
Data hold indication | "DH" mark on LCD |
Low battery indication | "Battery" mark on LCD |
Analog signal output | DC 100mV full scale to each range (Output impedance: less than 10kΩ) |
Auto power off | Approx. 10 minutes after last switch operation (Auto power off function can be released by the switch) |
Measuring method | Clamp type CT |
Zero adjustment | For DC current range by "0 ADJ" switch |