DC Current Sensor
AC Current Sensor
Measuring Instruments
SPEC. OF LEAKAGE CURRENT DETECTION | |
---|---|
Numbers of Monitoring Circuit | 1 Channel |
Setting Current Values | 10/30/50/100/200mA |
Measurement | DC Leakage Current |
Detection Accuracy | within±10%±1mA to each range |
Detection Period | less than 2 sec. at the time of 120% of setting value |
Recovery Value | 80%±5% of setting value |
Additional Time for Signal Output | 2-3 sec. |
SPEC. OF CT | |
---|---|
Inside Diameter | φ20mm |
Structure | Non-Split Core Type ZCT |
SPEC.OF WARNING DISPLAY & SIGNAL OUTPUT | |
---|---|
WARNING DISPLAY & SIGNAL OUTPUT | Warning Lamp (Red LED) lights and is kept lightening when leakage current exceeds the setting value for the period |
Numbers of Output Circuit | 1 circuit |
Output Method | Relay Contact (AC125V, 0.5A/DC24V, 1A), Resistance Loading |
GENERAL SPECIFICATION | |
---|---|
Power Supply Voltage | AC100V±10%, 50/60Hz |
Operating Temperature | 0~50℃, less than 85%RH (w/o condensation) |
Storage Temperature | - 20~60℃, less than 85%RH (w/o condensation) |
Withstanding Voltage | AC1000V, 1 minute between power input and case AC1000V, 1 minute between signal output and case |
Insulation Resistance | more than 100MΩ by DC500V insulation tester between power input and case more than 100MΩ by DC500V insulation tester between signal output and case |
Dimension & Weight | 85.5(H)x110(W)x 5(D)mm, Approx. 300gs. |
OTHER SPECIFICATION | Test Function: By pushing test switch, warning lamp lights and output signal becomes ON. Reset Fuction: By pushing reset switch, warning lamp goes out and can reset it. In case of operating when reset, warning lamp lights again. |