Split type AC Current Sensor
CTF-7NF AC Current measurements, AC 0.1~40A, φ7mm
FEATURES
Ultra compact size and high accuracy.
Easy installation in the distributing box.
Compliant with RoHS drective.
SPECIFICATIONS |
Rated Primary Current |
AC30A(50/60Hz) |
Applicable Current |
0.1A~30A |
Max. Capable Current |
50A |
Nominal CT Ratio |
3000:1 |
CT Inside Diameter |
φ7mm |
Applicable Frequency |
10Hz~5kHz |
Output Example |
AC100.0mV±1%(30A/10Ω) |
Phase Accuracy |
+2.5°±1.0°(30A/10Ω) |
Open Protection |
7.5V (Zener diode) |
Capable CT Open/Close |
Approx. 100 times |
Output Part |
Lead Wire: Approx. 200mm |
Rated Voltage |
Less than AC600V for low voltage circuit of coated wires |
Withstanding Voltage |
AC1500V/1 minute (between output terminal and outer case) |
Insulation Resistance |
More than 50MΩ by 500V insulation tester (between output terminal and outer case) |
Operation Temperature |
-20~60℃, less than 80%RH w/o condensation |
Dimension |
25.6×26.8×21.2mm |
Weight |
Approx. 20g |
Standard |
Compliant with RoHS directive |