Split type AC Current Sensor
Split type AC Current Sensor
CTF-6 AC Current measurements, AC 0.1~30A, φ6mm
CTF-10 AC Current measurements, AC 0.1~60A, φ9.5mm
CTF-16 AC Current measurements, AC 0.1~100A, φ14.5mm
CTF-24 AC Current measurements, AC 0.1~200A, φ24mm
CTF-5A AC Current measurements, AC 0.01~5A, 10mm×7.9mm
CTF-50A AC Current measurements, AC 0.1~50A, 10mm×9.5mm
CTF-100A AC Current measurements, AC 0.1~100A, 16mm×14.5mm
CTF-200A AC Current measurements, AC 1~200A, 24mm×24mm
CTF-400A AC Current measurements, AC 1~400A, 37mm×35.5mm
CTF-600A AC Current measurements, AC 1~600A, 37mm×35.5mm
CTF-7NF AC Current measurements, AC 0.1~40A, φ7mm
CTF-13NF AC Current measurements, AC 0.1~100A, φ13mm
Split type AC Current Transformer
CTS-100 General metering application, AC 100A,φ35mm, 1A output
CTS-200 General metering application, AC 200A,φ35mm, 1A output
CTS-300 General metering application, AC 300A,φ35mm, 5A output
CTS-400 General metering application, AC 400A,φ35mm, 5A output
CTS-600 General metering application, AC 600A,φ35mm, 5A output
CTF-100T General metering application, AC 100A,φ24mm, 1A output
CTF-200T General metering application, AC 200A,φ35mm, 1A output
CTF-400T General metering application, AC 400A,φ35mm, 1A output
Split type Pulse Current Sensor
Current Sensor for Outdoor Use
Zero Phase Current Transformer
Through Hole type AC Current Sensor
Clamp type AC Current Sensor
Other AC Current Sensor
Split type AC Current Sensor
CTF-6 AC Current measurements, AC 0.1~30A, φ6mm
FEATURES
For AC current and power measurements.
Ultra compact size and high accurate output linearity.
Easy installation in the distributing box.
Compliant with RoHS drective.
SPECIFICATIONS
Rated Primary Current
AC30A(50/60Hz)
Applicable Current
0.1A~30A
Max. Capable Current
50A
Nominal CT Ratio
3000:1
CT Inside Diameter
φ6mm
Applicable Frequency
10Hz~5kHz
Output Example
AC100mV±1%(30A/10Ω)
Phase Accuracy
+2.5°±0.5°(30A/10Ω/50Hz)
+2.1°±0.5°(30A/10Ω/60Hz)
Open Protection
7.5V (Zener diode)
Capable CT Open/Close
Approx. 100 times
Output Part
Lead Wire: Approx. 200mm
Rated Voltage
Less than AC600V for low voltage circuit of coated wires
Withstanding Voltage
AC2200V/1 minute (between output terminal and outer case)
Insulation Resistance
More than 50MΩ by 500V insulation tester (between output terminal and outer case)
Operation Temperature
-20~60℃, less than 80%RH w/o condensation
Dimension
19.3×31×26.4mm
Weight
Approx. 20g
Standard
Compliant with RoHS directive