Current Sensor for Outdoor Use
CT-41B Current Sensor for Outdoor Use
FEATURES
Equivalent to protection grade IP67
SPECIFICATIONS |
Rated Primary Current |
AC800A(50/60Hz) |
Rated Secondary Current |
0.2A |
Max. Capable Current |
800A |
CT Inside Diameter |
φ41mm |
Applicable Frequency |
50Hz~2kHz |
Comparative Error |
±0.5% In |
Phase Accuracy |
±1.0° In |
Overcurrent Intensity |
12.5kA / 2sec. |
Rated Burden (VA) |
0.64VA |
Open Protection |
24V (Zener diode) |
Output Part |
Lead Wire:Approx. 7000mm |
Rated Voltage |
Less than AC600V for low voltage circuit of coated wires |
Withstanding Voltage |
AC2000V/1 minute (between output terminal and Core) |
Insulation Resistance |
More than 100MΩ by 500V insulation tester (between output terminal and CT) |
Operation Temperature |
-20~60℃ |
Dimension |
97×134×42mm |
Weight |
Approx. 600g |
Standard |
Compliant with RoHS directive |