DC Current Sensor
AC Current Sensor
Measuring Instruments

| SPECIFICATIONS | |
|---|---|
| Fault Detection | Phase-to-phase short circuit fault, phase-to-ground fault, fault current magnitude and duration |
| Short circuit tripping current | 200A/600A/800A/1000A, Adjustable, Default 200A |
| Detection accuracy | When 200A, ±5% |
| Ground fault tripping current | 40A/80A/120A/160A, Adjustable, Default 40A |
| Detection accuracy | When 40A, ±5% |
| Reception delay time for Short circuit and Ground fault | 40ms/80ms/100ms/200ms, Adjustable, Default 40ms |
| Applicable load current | AC2KA |
| Reset | Remote control reset, MODBUS…Transient/Permanent short-circuit & earth-fault Remote DI Reset, SCADA DC9-38V wide voltage input…Transient/Permanent short-circuit & earth-fault Load Current Reset, >10A…Permanent:short-circuit AC Voltage Reset, AC220-240V recovery…Permanent:short-circuitButton Reset, push-button short press for 1s…Transient/Permanent short-circuit & earth-fault Timing Reset, 2min(for test), 12h, 24h, 48h, adjustable by DIP switch…Transient: short-circuit & earth-fault |
| Operating circuit voltage | AC5~38kV(50/60Hz) |
| Operating temperature | -40~70℃ |
| CT type | Short circuit current sensor:φ80mm, Earth Current Sensor:φ110mm |
| Power supply | Lithium battery 3.6V/ 2.7Ah replaceable, External power supply:5~36VDC |
| Size | Main body: 100*120*45mm, Short circuit current sensor:φ80mm-2m cable, Earth Current Sensor:φ110mm-2m cable |
| IP Protection | Main body: IP54, Sensors: IP68 |
| Standard | IEC 60529:1989+AMD1:1999+AMD2:2013 / IEEE Std 495 (2007) ETSI EN 300 328 V2.2.2 / EN 62479:2010 EN IEC 62311:2020 / EN IEC 61326-1:2021 EN 61000-4-2:2009 / EN IEC 61000-4-3:2020 EN 61010-1:2010/A1:2019/ EN 61010-2-032:2012 |
| SCADA contact | 2-relays contact, Max. 250VAC/30VDC/ 5A |
| Communication protocol | RS485: Data bits 8/Stop bits 1/Parity none/Baud Rate:9600 Protocol:MODBUS RTU |