Leakage Current Monitor

MULFI-38 Line fault indicator for MV underground distribution linesLine fault indicator for MV underground distribution lines

FEATURES

+The fault information will also be sent to SCADA system by external connection with IP Modem or RTU/FRTU.
+When the sensors detect short-circuit and earth-fault, it transmits the fault information to display unit by cable immediately. Then the LED starts to flash, and the display unit send the fault signal to SCADA system by relay output or MODBUS at the same time.
+The fault indicator will also be shown on the Map location or Mimic diagram of SCADA system, it helps the user to identify the faulty section quickly.
DOWNLOAD
SPECIFICATIONS
Fault Detection Phase-to-phase short circuit fault, phase-to-ground fault, fault current magnitude and duration
Short circuit tripping current 200A/600A/800A/1000A, Adjustable, Default 200A
Detection accuracy When 200A, ±5%
Ground fault tripping current 40A/80A/120A/160A, Adjustable, Default 40A
Detection accuracy When 40A, ±5%
Reception delay time for Short circuit and Ground fault 40ms/80ms/100ms/200ms, Adjustable, Default 40ms
Applicable load current AC2KA
Reset Remote control reset, MODBUS…Transient/Permanent short-circuit & earth-fault
Remote DI Reset, SCADA DC9-38V wide voltage input…Transient/Permanent short-circuit & earth-fault
Load Current Reset, >10A…Permanent:short-circuit
AC Voltage Reset, AC220-240V recovery…Permanent:short-circuitButton Reset, push-button short press for 1s…Transient/Permanent short-circuit & earth-fault
Timing Reset, 2min(for test), 12h, 24h, 48h, adjustable by DIP switch…Transient: short-circuit & earth-fault
Operating circuit voltage AC5~38kV(50/60Hz)
Operating temperature -40~70℃
CT type Short circuit current sensor:φ80mm, Earth Current Sensor:φ110mm
Power supply Lithium battery 3.6V/ 2.7Ah replaceable, External power supply:5~36VDC
Size Main body: 100*120*45mm,
Short circuit current sensor:φ80mm-2m cable, Earth Current Sensor:φ110mm-2m cable
IP Protection Main body: IP54, Sensors: IP68
Standard IEC 60529:1989+AMD1:1999+AMD2:2013 / IEEE Std 495 (2007)
ETSI EN 300 328 V2.2.2 / EN 62479:2010
EN IEC 62311:2020 / EN IEC 61326-1:2021
EN 61000-4-2:2009 / EN IEC 61000-4-3:2020
EN 61010-1:2010/A1:2019/ EN 61010-2-032:2012
SCADA contact 2-relays contact, Max. 250VAC/30VDC/ 5A
Communication protocol RS485: Data bits 8/Stop bits 1/Parity none/Baud Rate:9600
Protocol:MODBUS RTU