DC Current Sensor
AC Current Sensor
Measuring Instruments

| SPECIFICATIONS | |
|---|---|
| Measuring function | AC leakage current(By 2CT) AC leakage current (By main CT) AC load current  | 
| Measuring ranges | 0 ~ 200mA/2000mA (Leakage current) 0 ~ 20mA/200A (Load current)  | 
| Display | LCD max. 9999 count with annunciators | 
| Accuracy | (23 ℃ ±5 ℃ , less than 85%RH) Function/Range/Resolution/Accuracy(50/60Hz) 2CT/AC1000mA/0.1mA/±1% rdg ± 10dgt 2CT/AC10A/0.001A/±1% rdg ± 10dgt Main CT/AC20A/0.01A/±1% rdg ± 10dgt Main CT/AC200A/0.1A/0 ~ 100A:±1% rdg ± 10dgt,101 ~ 150A : ± 3% rdg ± 10dgt,151 ~ 200A : ± 6% rdg ± 10dgt  | 
| AC conversion | True rms responding | 
| A/D conversion | Dual slope integration method | 
| Jaw opening capability | 40mm φ (Main CT) 5mm φ (Auxiliary CT)  | 
| Over range indication | Over range indication | 
| Data hold indication | "DH" mark on LCD | 
| Auto power off | Approx. 10 minutes after power on | 
| Low battery indication | "B" mark on LCD | 
| Sampling rate | 2 time/sec. | 
| Limitation of circuit voltage | Less than AC/DC 500V | 
| Withstanding voltage | AC 2000V/1 minute between CT and outer case | 
| Operating temperature | 0 ~ 40 ℃ , < 85%RH (without condensation) | 
| Storage temperature | -10 ~ 60 ℃ < 70%RH (without condensation) | 
| Power supply | LR03,AM-4 or AAA size Alkaline battery×3 | 
| Size | 64(W)×195(H)×24(D)mm(Main CT) 25(W)×114(H)×19(D)mm(Auxiliary CT)  | 
| Weight | Approx.190g | 
| Accessories | Carrying case:1 Instruction manual:1 Batteries:3 Auxiliary CT (CTP-05-2) with 1.5m lead cable:1  |