DC Current Sensor
AC Current Sensor
Measuring Instruments

![]()  | 
Select a measurement point, which registered in advance, and save measurement data. It can be utilized as a guide for deterioration diagnosis, in addition to improving efficient maintenance management. | 
![]()  | 
By examining influences of harmonics or noises, it is possible to investigate diagnosis and cause of troubles at facilities. | 
| SPECIFICATIONS | |
|---|---|
| Measuring function | Line current Leakage current  | 
| CT inside diameter | φ40mm | 
| AC current range | 30mA / 300mA / 3A / 30A / 300A | 
| Minimum resolution | 0.01mA | 
| Accuracy | AC 30mA / 300mA / 3A / 30A ±1.2%rdg±5dgt AC 300A 0~200A : ±1.2%rdg±5dgt 200~250A : -3.0%rdg±5dgt 250~300A : -5.0%rdg±5dgt 23℃±5℃ 80%RH or less (50 / 60Hz)  | 
| Interface | Bluetooth 4.2 | 
| Filter function | Band pass filter fo=55Hz (Automatically starts when the power is turned on) | 
| Max memory function | "Max" mark on LCD with maximum value | 
| Other function | Over range display, Data hold, Low battery indication, Auto power off | 
| Sampling rate | Two times / second | 
| Safety standard | EN61010 Installation category IV 600V or category III 1000V  | 
| Operating circuit voltage | Less than AC500V (Isolated electric wire) | 
| Operating temp & humidity Range | 0~50℃ Less than 85%RH (w / o condensation) | 
| Power supply | CR2450×1 | 
| Dimension / Weight | W61×H206×D35mm Approx.260g  | 
| Accessories | Carrying case, Instruction manual |