We specialize in Current Sensors, CT Sensors, and Measuring Instruments.

HOME
back
Clamp type AC Current Sensor/for Leakage Current Measurements(ZCT Series)

ZCT-150T Leakage current measurements of bus bar, AC 1mA~50A, 32mm×150mm

FEATURES

Easy installation.
For leakage current measurements of bus bar
Unique split and track type ZCT sensor
High sensitive and least affection from external magnetic field
DOWNLOAD
SPECIFICATIONS
Rated Primary Current AC50A
Applicable Current 1mA~50A
Max. Capable Current 60A
Secondary Windings 2000Turns
CT Inside Diameter 32×150mm
Applicable Frequency 10Hz~1kHz
Output Example AC52.1mV±2%(10A/10Ω)
Recommendable Load Resistor 10Ω
Output Part M4 Terminal
Rated Voltage Less than AC600V for low voltage circuit of coated wires
Withstanding Voltage AC2200V/1 minute (between output terminal and CT)
Insulation Resistance More than 100MΩ by 500V insulation tester (between output terminal and CT)
Operation Temperature 0~60℃, less than 80%RH w/o condensation
Dimension 220×114×50mm
Weight Approx. 1300g
PAGE TOP