Clamp type AC Current Sensor/for Power Monitor
CT-80PB Current measurements and power monitor of main cable, AC 1A~500A, 80mm×74mm
FEATURES
BIG CT WINDOW
AC 1A~500A
Current measurements of main cable
SPECIFICATIONS |
Rated Primary Current |
AC500A |
Applicable Current |
1A~500A |
Max. Capable Current |
600A |
Secondary Windings |
2000Turns |
CT Inside Diameter |
80×74mm |
Applicable Frequency |
10Hz~5kHz |
Output Example |
AC50.4mV±2%(10A/10Ω) |
Recommendable Load Resistor |
1~10Ω |
Output Part |
Lead Wire:Approx. 1000mm |
Rated Voltage |
Less than AC600V for low voltage circuit of coated wires |
Withstanding Voltage |
AC2200V/1 minute (between output terminal and CT) |
Insulation Resistance |
More than 100MΩ by 500V insulation tester (between output terminal and CT) |
Operation Temperature |
0~60℃, less than 80%RH w/o condensation |
Dimension |
138×224.5×34mm |
Weight |
Approx. 500g |