We specialize in Current Sensors, CT Sensors, and Measuring Instruments.

HOME
back
AC High Voltage Clamp Meter

HCL-3000+ High Insulation Digital Clamp Tester33mmφCT, ACA

AC Small current measurements for high voltage circuit

FEATURES

・AC current measurements for 20mA~200A.
・Easy operation, Push to Open and Pull to Disconnect Mechanism.
・Safe AC current measurements for high voltage circuit (AC80 to 7000V).
DOWNLOAD
SPECIFICATIONS
Measuring method Dual slope integration mode
Display 3.5 digit LCD, max. reading of 1999
Measuring ranges AC 2000 mA/20 A/2000 A
Accuracy 23℃±5℃ 80%RH or less (50/60Hz)
Range/Resolution/Accuracy
2000 mA//1mA/±2%rdg±5dgt
20 A//0.01A/±2%rdg±5dgt
200 A//0.1A/±2%rdg±5dgt
Inside diameter of CT φ33mm
Withstanding voltage AC 14000V/1 minute
Over range indication "OL" mark on LCD
Data hold indication "DH" mark on LCD
Low battery indication "B" mark on LCD
Sampling rate 2 times/sec
Operating temperature 0~40℃, < 80%RH (without condensation)
Power supply AA manganese batteryUM-3×2
Dimension 76(W)×311(H)×42(D)mm
Weight Approx. 285g
Accessories Carrying case, Batteries, Instruction manual
PAGE TOP