CTF-13NF AC Current measurements, AC 0.1~100A, φ13mm
FEATURES
Ultra compact size and high accuracy.
Easy installation in the distributing box.
Compliant with RoHS drective.
SPECIFICATIONS |
Rated Primary Current |
AC100A(50/60Hz) |
Applicable Current |
0.1A~100A |
Max. Capable Current |
150A |
Nominal CT Ratio |
3000:1 |
CT Inside Diameter |
φ13.8mm |
Applicable Frequency |
10Hz~5kHz |
Output Example |
AC333.3mV±1.0%(100A/10Ω) |
Phase Accuracy |
+0.7°±0.5°(100A/10Ω) |
Open Protection |
7.5V (Zener diode) |
Capable CT Open/Close |
Approx. 100 times |
Output Part |
Connector: S02B-PASK-2 |
Rated Voltage |
Less than AC600V for low voltage circuit of coated wires |
Withstanding Voltage |
AC2200V/1 minute (between output terminal and outer case) |
Insulation Resistance |
More than 50MΩ by 500V insulation tester (between output terminal and outer case) |
Operation Temperature |
-20~60℃, less than 80%RH w/o condensation |
Dimension |
37.5×44.2×38.9mm |
Weight |
Approx. 75g |
Standard |
Compliant with RoHS directive |