Current Sensor for Outdoor Use

MLFI-69X Line fault indicatorA monitoring device for detecting earth faults in power distribution lines. Also includes a current value monitoring function.

High voltage earth fault monitoring device

FEATURES

・It can be monitoring between long time periods because it is powered directly from the power distribution line. A lithium battery is included as standard equipment as spare power source for operation in the event of a ground fault.

・For monitoring operation, it will be necessary to connect the DCU.
The DCU equipped the long distance communication IEC101/IEC104/DNP3.0/Modbus to connect with SKADA system.

オープン価格

INQUIRY
Electrical characteristics
Short-circuit Trip(Phase to Phase)/Measurement Current 50~1200A adjustable, 1A step, 150A default
Accuracy 0A~300A ±3A
300A~800A ±1%
Earth-fault Voltage Drop (Phase to Ground) Adjustable: 1% step, 30% default
Earth-fault Response Delay Adjustable: 1 second step, 30s default
Physical specifications
Protection Class IP68
Operation Temperature Range -40~+70℃
Power Supply Main:
Automatic power supply from distribution or transmission lines
Sub:
Lithium battery type AA 3.6V / 9Ah(Battery Life 10 years), replaceable
Weight Indicator:
Approx. 600g/1ea
DCU:
Approx. 3.6Kgs/1ea
Dimensions Indicator:
Width: 93mm
Height: 170mm
DCU:
Width:200mm
Height:300mm
Length:148mm
Applied cable diameter 6mm~42mm
Blinking Frequency 10 per minute, adjustable
Use voltage General:
38kV
Customizable:
44/69/110kV
Withstand current 31.5KA/4s
Other specifications
Indication Unit Reset 1. manual by magnet.
2. remote reset through SCADA system
3. time reset: adjustable, 1 second step, 24h default, max. 48h
4. Auto delay reset after repower, 1 second step, 30s default
max 5min, only for permanent fault
Complied standard According to IEEE495-2007
Communication 433MHz from indicators toDCU
2.5G/3G/4G from DCU toSCADA
Communication Protocol Indicator to DCU: private
DCU to SCADA: IEC101, IEC104, DNP3.0,Modbus