DC Current Sensor
AC Current Sensor
Measuring Instruments
SPECIFICATIONS | |
---|---|
Rated Primary Current | AC100A |
CT Inside Diameter | φ31mm |
Applicable Frequency | 50/60Hz |
Output Characteristic(RL=530Ω) | Primary Input Current 0.1A / Criterion Output 50mV / Tolerance +5%-10% Primary Input Current 0.2A / Criterion Output 100mV / Tolerance +5%-10% Primary Input Current 0.4A / Criterion Output 200mV / Tolerance +5%-10% Primary Input Current 0.8A / Criterion Output 400mV / Tolerance +5%-10% |
Load Resisance | 530Ω |
Equilibrium Characteristic | Less than 30mV(max. residual voltage when AC42mA is piled up to the rated current) |
Output Part | M4 Terminal |
Applicable Circuit | Single Phase/Three Phase |
Rated Voltage | Less than AC600V for low voltage circuit of coated wires |
Withstanding Voltage | AC2200V/1 minute (between output terminal and CT) |
Insulation Resistance | More than 50MΩ by 500V insulation tester (between output terminal and CT) |
Operation Temperature | -10~60℃, 45~80%RH w/o condensation |
Dimension | 130×100.5×34.7mm |
Weight | Approx. 560g |
Standard | Compliant with RoHS directive |