直流電流センサ
交流電流センサ
計測器

| SPECIFICATIONS | |
|---|---|
| Withstanding Voltage | AC 1500V, 1 minute (between detecting tip and earth clip) |
| Insulation Resistance | 10MΩ or more by DC 500V insulation tester (between detecting tip and earth clip) |
| Size and Weight | 129 (L)×20 (W)×19.5 (D)mm, approx. 30g |
| Operating Temperature | 0℃~40℃ |
| Power supply | 1.55V (LR-44)×2 |
| Power consumption | Approx. 60 hours continuous |
| Accessories | Soft case:1 Instruction manual:1 Alligator clip:1 Battery:2 |
| Detectable voltage range(50/60Hz) | For insulation cover AC 50~500V phase to earth For bare terminal AC 0~300V phase to earth |
| Minimum detectable voltage | AC40V (Factory setting)(Sensitivity is adjustable) |
| Judgment value for insulation fault | More than 10μA, floating to the human body ("L" lamp will turn on) |
| Detection signal | Flashing of red LED light and intermittent beeper (For both voltage detection and insulation fault) |