We specialize in Current Sensors, CT Sensors, and Measuring Instruments.

HOME
back
Partial discharge detector

SE-55FD Partial discharge easy detector

The SE-55FD detects ultrasonic waves generated during discharge due to poor contact/insulation fault of high-voltage electrical equipment, accessories, etc., and displays the sound pressure level by an LED bar meter, and at the same time, the sound emitted from the sound port determines the discharge location and magnitude. It is possible to detect partial discharge.

FEATURES

・It has an LED pointer and can easily find the fault point.
・Since SE-55FD captures the discharge sound synchronized with the commercial frequency, the effect of ambient noise is reduced to 1/30 compared to SE-55.
・SE-55FD has a data output terminal, you can connect it to a data logger equipped with a stereo mini plug and available to import the data to your computer.
DOWNLOAD
SPECIFICATIONS
Reception frequency 40kHz ± 1kHz
Directivity half width Less than ± 5°
Measurable distance 1~2m
Display method Bar LED
Reception sensitivity 35~75bB
Display resolution 5dB
Reception sensitivity setting distance 1m
Target setting method LED light pointer
Power supply AA alkali battery*4pcs
Operating temperature range 0~40℃ Less than 85%RH w/o condensation
Storage temperature range -10~50℃ Less than 85%RH w/o condensation
External dimensions Φ66xH215mm
Weight 280g
Standard Accessories Battery, soft carrying case, instruction manual
PAGE TOP