We specialize in Current Sensors, CT Sensors, and Measuring Instruments.

HOME
back
AC Leakage Clamp Meter

RLM-10 Flexible Leakage/Line Current Tester

Flexible leakage current tester (CE)

FEATURES

● Freely Bending with Rogowski Method Flexible Clamp Sensor
● Useful for Difficult Access Locations with Wide Rages
● Even Coreless Coil but Least Influence from External Magnetic Field and Residual Current
● Superior Flexible CT enables Leakage Current Measurement
● Backlight Function useful for measurement in the dark place
DOWNLOAD
SPECIFICATIONS - CURRENT DETECTION PART
Sensoring Method Flexible Split-Core Type
Inside Diameter φ210mm (total length approx. 650mm)
Influence of Residual Current Less than 0.5A (at AC 50A, the point where influence is most
receivable)
Withstanding Voltage AC 2200V/1 minute
Length of Lead Wire Approx. 2m between CT and Measuring Part
SPECIFICATIONS - MEASURING PART
Measuring Function AC Line Current, AC Leakage Current
Measuring Method Dual Integration Mode
Measuring Range AC 3000mA/30A/300A/3000A (50/60 Hz)
Range Selection 4 Range Manual by Rotary Switch
Sampling Rate 2 Times/sec.
Display LCD max. 3200 reading with annunciators
Over Range Indication "OL" mark on LCD
Data Hold Indication "DH" mark on LCD
Low Battery Indication "B" mark on LCD
Data Hold Function by "DH" Switch
Filter Function by Filter Switch to cut hi-frequency (Low Pass Filter for cut off
150 Hz)
Backlight Function By pressing this switch, back light appears on LCD display and
will get off by pressing this switch once again.
Signal Output DC 300mV full scale to each range
(Output impedance : less than 10KΩ)
Auto Power Off Approx. 10 minutes after power on (this function is cancelled in
case of using recorder cable for signal output)
SPECIFICATIONS - GENERAL SPECIFICATION
Circuit Voltage Less than AC 600V
Operating Temperature 0~40℃, < 85%RH without condensation
Storage Temperature -10~60℃, < 70%RH without condensation
Withstanding Voltage AC 2200V/1 minute
Power Supply 1.5V (“AA” size, UM-3) x 6
Dimension (Measuring Part) 159(W)×105(H)×53(D) mm
Standard accessories Battery (UM-3 x 6), Instruction Manual , Carrying Cas
SPECIFICATIONS - ACCURACY
ACCURACY 23℃±5℃, less than 80%RH
AC 3000mA / 1mA / ±3%rdg±5dgt
AC 30A / 0.01A / ±2.5%rdg±5dgt
AC 300A / 0.1A / ±2.5%rdg±5dgt
AC 3000A 1A / ±2.5%rdg±5dgt
Signal Output ±2% F.S.
PAGE TOP