search WWW
search Multi Site
Clamp type AC current sensor/ With DC voltage output
AC CURRENT SENSOR
Clamp type AC current sensor / With voltage output
RCT-18
(Leakage current measurements, AC 0.1mA~100mA, φ18mm, DCV output)
ACT-5H
(5A circuit measurements, AC 0.1A~5A, φ23mm. DC 5V output)
ACT-50H
(Current measurement of feeder, AC 1A~50A, φ23mm, DC 5V output)
List of AC Current sensor
List of DC Current sensor
HOME
Page to TOP
ACT-50H
PRODUCTS
FEATURES
For current measurements of the control board
AC 1A~50A
DC 5V full scale output
SPEC
SPECIFICATIONS
Measuring Range
:
AC 1A~50A
CT Inside Size
:
φ23mm
Accuracy and Output Voltage
:
DC 5V f.s (0.1V/A) ±2%
Applicable Frequency
:
50/60Hz
AC Conversion
:
Average sensing
Input Resistance
:
More than 1MΩ
Withstanding Voltage
:
AC 2200V, 1 minute
(between CT and output)
Insulation Resistance
:
DC500V,more than 100MΩ
(between CT and output)
Operating Temperature
:
0~60℃ less than 80%RH
Without condensation
Output Cable
:
3wire shield cable(3m)
Dimension
:
48×146×20mm
Weight
:
85gs
Power Supply
:
DC 24V(external)