search WWW
search Multi Site
Clamp type AC current sensor/ For leakage current measurements(ZCT Series)
AC CURRENT SENSOR
Clamp type AC current sensor / For leakage current(ZCT Series)
ZCT-30
(Current measurements of feeder, AC 1mA~100A, φ30mm)
ZCT-30S
(Current measurements of feeder, AC 1mA~100A, φ30mm)
ZCT-140
(Current measurements of feeder, AC 1mA~300A, φ40mm)
ZCT-140S
(Current measurements of feeder, AC 1mA~300A, φ40mm)
ZCT-40SQ
(Current measurements of feeder, AC 1mA~50A, φ40mm)
ZCT-80
(Current measurements of main cable, AC 1mA~1000A, 80mm×74mm)
ZCT-1100
(Current measurements of main cable, AC 1mA~3000A, 128mm×108mm)
ZCT-150T
(Leakage current measurements, AC 1mA~50A, 32mm×150mm)
List of AC Current sensor
List of DC Current sensor
HOME
Page to TOP
ZCT-150T
PRODUCTS
FEATURES
Easy installation.
For leakage current measurements of bus bar
Unique split and track type ZCT sensor
High sensitive and least affection from external magnetic field
■ CHARACTERISTIC OF OUTPUT VOLTAGE
SPEC
SPECIFICATIONS
Measuring range
:
AC 1mA~50A
Output Characteristic
:
Refer to the drawing
Output Example
:
AC52.1mV±2% (10A/10Ω)
Nominal CT Ratio
:
4000:1
CT Inside Size
:
32mm×150mm
Max. Input Current
:
AC 60Arms continuous
Applicable Frequency
:
10Hz~1KHz
Max. Circuit Voltage
:
Less than AC600V( low voltage circuit)
Withstanding Voltage
:
AC 2200V,1 minute
(between CT and output)
Insulation Resistance
:
More than 100MΩ by 500V insulation tester
(between CT and output)
Operation Temperature
:
-10~50 ℃, less than 80%RH
Without condensation
Material of Outer Case
:
ABS Resin
Material of Core
:
Parmalloy
Output
:
Output terminals
Dimension/Weight
:
230×120×50mm/Approx. 1300gs.