search WWW
search Multi Site
Split and low V/A type AC current transformer (CTS Series)
AC CURRENT SENSOR
Sprit and low V/A type AC current transformer(CTS Series)
CTS-100
(General metering application, AC 100A, φ35mm, 1A output)
CTS-200
(General metering application, AC 200A, φ35mm, 1A output)
CTS-300
(General metering application, AC 300A, φ35mm, 5A output)
CTS-400
(General metering application, AC 400A, φ35mm, 5A output)
CTS-600
(General metering application, AC 600A, φ35mm, 5A output)
List of AC Current sensor
List of DC Current sensor
HOME
Page to TOP
CTS-100
PRODUCTS
FEATURES
1A output for metering application.
Short circuit switch for secondary output is provided for safe operation.
High accurate transformer for the application of first class meter.
Easy installation by metal fitting.
■ CHARACTERISTIC OF OUTPUT VOLTAGE
SPEC
SPECIFICATIONS
Rated Primary Current
:
AC 100A
Rated Secondary Current
:
1A
Rated Burden (VA)
:
0.2VA
Accuracy
:
±1.0%In
Phase Accuracy
:
±1.0°In
Output Characteristic
:
Refer to the drawing
CT Inside Diameter
:
φ35mm
Max. Input Current
:
AC 120A
Open Circuit Protection
:
Short-circuit switch for output
Applicable Frequency
:
50/60Hz
Max. Circuit Voltage
:
Less than AC600V for insulated cable
Withstanding Voltage
:
AC 2200V/1 minute
(between output terminal and outer case)
Insulation Resistance
:
More than 100MΩby 500V insulation tester
(between output terminal and outer case)
Operational Temperature
:
-10~50℃, less than 80%RH
Without condensation
Material of Outer Case
:
ABS Resin (Flame rating:compliant with UL-94V-0)
Material of Core
:
Silicon Steel
Dimension/Weight
:
127(W)×40(D)×95(H)mm/ Approx. 550gs.
Standard
: