Multi Measuring Instruments Co.,Ltd. Japanese Chinese
Google
 

Split type AC current sensor (CTF Series)

CTF-100A

PRODUCTS
CTF-100A FEATURES
  • Suitable for current measurements of feeder.
  • Wire stopper is equipped for the slipping protection.
  • The special connector is not necessary as the output terminals are provided.
  • Open circuit protection and nonflammable plastic material.
■ CHARACTERISTIC OF OUTPUT VOLTAGE
CHARACTERISTIC OF OUTPUT VOLTAGE
SPEC
SPECIFICATIONS
Applicable Current : AC 0.1~100Arms
Output Characteristic : Refer to the drawing
Output Example : AC33.3mA±1% (100A)
Phase Accuracy : -0.7°±0.5°(100A)
Nominal CT Ratio : 3000:1
CT Inside Diameter : φ16mm
Max. Input Current : 200Arms continuous
Open Circuit Protection : 7.5V
Applicable Frequency : 10Hz~5kHz
Max. Circuit Voltage : Less than AC600V for insulated cable
Withstanding Voltage : AC 2200V/1 minute
(between output terminal and outer case)
Insulation Resistance : More than 100MΩ by 500V insulation tester
(between output terminal and outer case)
Operational Temperature : -10~50 ℃, less than 80%RH
Without condensation
Material of Outer Case : P.P. (Flame rating:compliant with UL-94V-O)
Material of Core : Ferrite
Dimension/Weight : 31(W)×30(D)×54(H)mm /Approx. 85gs.
Standard : Compliant with RoHS directive