Multi Measuring Instruments Co.,Ltd. Japanese Chinese
Google
 

Earth resistance clamp tester

Clamp Earth Tester

PRODUCTS
Model MET-2 (CE)
Simple earth resistance measurements without auxiliary rods and test leads.
Earth Clamp Tester. Model MET-2 (CE)
FEATURES
  • Test frequencies are selected automatically to minimize erroneous measurements.
  • Earth resistance measurements for secondary side of the extra-high voltage transformer, equipotential bonding conductors and both single and multi-grounded systems.
  • Leakage current and load current measurements with 200mA, 2000mA and 20A ranges.
  • Data memory and auto power off function.
  • 10Ω and 300Ω earth resistance ranges.
Show detail Catalog PDF Measuring principle PDF Measuring example PDF
DETAIL
example
SPEC
SPECIFICATIONS
Measuring function : Earth Resistance, AC Current (Load and Leakage)
Measuring method : Dual slope integration mode
Safety standard : IEC 61010-1, IEC61010-2-032
Installation categoryII, 600V or CATⅢ 300V
Sampling : Approx. 2 times/sec. for AC current
Measuring time : Approx. 30 second for earth resistance
Display : LCD, 16 letters/characters × 2 lines
with contrast adjuster
Over range indication : "OVER" on LCD
Low battery indication : "B" mark on LCD
Data hold indication : "DH" mark on LCD
Memory function : 40 measuring data can be stored and displayed
Accuracy : (23℃ ± 5℃, 80% RH or less)
Earth resistance :
Range Resolution Accuracy
10Ω 0.01Ω 0.1~1Ω :±0.1Ω
1~10Ω :±0.5Ω
300Ω 0.1Ω 10~50Ω :±2.0Ω
50~150Ω :±5.0Ω
150~200Ω :±20Ω
200~300Ω :±30Ω
AC current :
Range Resolution Accuracy
200mA 0.1mA 3% rdg ± 8dgt
2000mA 1mA 2% rdg ± 8dgt
20A 0.01A 2% rdg ± 8dgt
Measurement CT : φ34mm with 2.5m lead
Injection CT : φ34mm with 2.5m lead, Auto sweep 4KHz~200kHz
Injection signal level : Approx. 320mVp-p
Storage temperature : -10℃~60℃, < 80% (without condensation)
Operating temperature : 0℃~40℃, < 80%RH ( without condensation)
Limitation of circuit voltage : Less than 600V
Withstanding voltage : AC 3700V, 1 minute (between CT core and outer case)
Insulation resistance : More than 100MΩ (between CT core and outer case)
Power supply : Ni-Cad battery (1.2V × 5)
Battery charger : AC200V~240V (50/60Hz)
Auto power off function : Approx. 5 minutes later after power on
Power consumption : Approx. 380mA(Earth resistance measurement)
Battery life : Approx.400 times measurements under full charged condition (Subject to the times of charging and discharging)
Size and weight :
Measurement CT : 90.5(W)×165(H)×38(D)mm, approx.460g
Injection CT : 90.5(W)×165(H)×38(D)mm, approx.440g
Main unit : 190(W)×140(H)×42 (D)mm, approx.800g
Accessories :
Measurement CT : 1
Injection CT : 1
Battery charger : 1
Carrying case : 1
Subsidiary lead wire : 1
Instruction manual : 1
Optional accessory : Subsidiary lead wire