search WWW
search Multi Site
AC/DC Clamp tester/leaker
AC/DC Clamp tester/leaker
(for AC/DC current and leakage current)
Model 230 AC/DC Mini clamp tester
(23mmφCT, ACA, DCA)
Model 240 AC/DC Mini clamp tester
(30mmφCT, ACA, DCA)
Model 250 AC/DC Mini clamp tester
(40mmφCT, ACA, DCA)
Model 260 AC/DC Digital clamp tester
(55mmφCT, ACA, DCA, ACV, DCV, Hz, Ω)
Model 270 AC/DC Digital clamp tester
(55mmφCT, ACA, ACV/True rms, DCA, DCV, Hz, Ω)
Model 280 AC/DC Mini clamp tester
(30mmφCT, ACA, DCA ACV, DCV, Ω)
Model 290RMS AC/DC Digital clamp tester
(30mmφCT, ACA, ACV/True rms, DCA, DCV, , Ω)
Model 600 AC/DC Digital clamp leaker
(30mmφCT, AC/DC leakage current)
Model 700 AC/DC Digital clamp milliammeter
(5mmφCT, AC/DC leakage current)
Model 730 AC/DC Digital clamp milliammeter
(30mmφCT, AC/DC leakage current)
List of MEASURING INSTRUMENTS
HOME
Page toTOP
AC/DC Mini Digital Clamp Tester
PRODUCTS
AC/DC Current, 20A/200A, 23mmφ CT
Model 230
FEATURES
23mmφCT window and ultra compact size.
Data-hold function. Especially useful when working in dark or hard to get areas.
Accurate gearing mechanism for closing of CT.
Best tool for automotive service.
≫
Show detail
≫
Catalog PDF
DETAIL
SPEC
SPECIFICATIONS
Measuring method
:
Dual slope integration mode
Display
:
3.5 digit LCD, max. reading of 1999
Range
:
AC/DC 0~20A/200A
Jaw opening capability
:
23mmφ
Over range indication
:
Blanking of all digits except MSD 1
Maximum indication
:
1999
Low battery indication
:
"B" mark on LCD
Data hold indication
:
"DH" mark on LCD
Sampling
:
2 times/sec
Withstanding voltage
:
AC 1000V 1 minute max. (Between the core of CT and outer case)
Insulation resistance
:
10MΩ or more(Between internal circuit and core of CT)
Limitation of circuit voltage
:
Less than AC/DC 500V
Operating temperature
:
0℃ to 40℃, 80%RH max. ( Without condensation )
Storage temperature
:
-10℃ to 60℃, 70%RH max. ( Without condensation )
Power supply
:
1.55V (SR-44, LR-44)×2
Power Consumption
:
7mW
Battery life
:
SR-44 (30 hours), LR-44 (16 hours)
Size
:
48(W)×146(H)×20(D)mm
Weight
:
Approx. 100g
Accessories
:
Soft case
:
Instruction manual
:
1
Batteries LR-44(1.55V)
:
2
AC Current
:
(Accuracy 23℃±5℃, 80%RH or less)
Range
Resolution
Accuracy(50/60HZ)
Accuracy(20~500Hz)
Max. input
20A
10mA
±1.0% rdg±5 dgt
±1.0% rdg±5 dgt
500A peak
200A
100mA
±1.5% rdg±5 dgt
(0~150.0A)
±2.0% rdg±5 dgt
(0~150.0A)
±2.5% rdg±5 dgt
(150.1~199.9A)
±3.5% rdg±5 dgt
(150.1~199.9A)
DC Current
:
(Accuracy 23℃±5℃ 80%RH or less)
Range
Resolution
Accuracy
Max. input current
20A
10mA
±1.0% rdg±3dgt
500A peak
200A
100mA
±1.5% rdg±3 dgt(0~150.0A)
±2.5% rdg±3dgt(150.1~199.9A)