Multi Measuring Instruments Co.,Ltd. Japanese Chinese
Google
 

AC clamp leaker

Universal Clamp Tester

PRODUCTS
AC Leakage Current /Load Current
30/300mA, 30/300A, 40mmφCT and U type CT
Model 310
Universal Clamp Tester. Model 310
FEATURES
  • The unique U type CT enabled to measure the load current of single or three phase cable without separating the cable to the wires.
  • Leakage current measurements with least affection from the external magnetic field.
  • Wide current measurements.(AC0.01mA-300A)
Show detail Catalog PDF
DETAIL
SPEC
SPECIFICATIONS
Measuring method : Dual slope integration mode
Display : 3.5 digit LCD, max. reading of 3200
Over range indication : "OL" mark on LCD
Low battery indication : "Battery" mark on LCD
Data hold indication : "DH" mark on LCD
Sampling : 2 times/sec(Digital display)
12 times/sec(Bar graph display)
Withstanding voltage : AC 2200V 1 minute max. (Between the core of CT and outer case)
Operating temperature : 0℃ to 40℃, 80%RH max. ( Without condensation )
Storage temperature : -10℃ to 60℃, 70%RH max. ( Without condensation )
Power supply : 1.55V (SR-44, LR-44)×2
Power Consumption : 5mW
Auto power off : Approx. 10 minutes later after power on
Battery life : Approx. 50 hours(LR-44)
Size : 64(W)×180(H)×21(D)mm
Weight : Approx. 135g
Accessories :
Soft case : 1
Instruction manual : 1
Batteries LR-44(1.55V) : 2
40mmφCT
Range : AC 0~30/300mA, 30/300A, 2range manual
Jaw opening capability : 40mmφ
Accuracy : 23℃±5℃ 80%RH or less (50/60Hz)
Range Resolution Accuracy
AC 30/300mA 0.01mA ±1.2% rdg ± 5dgt
AC 30/300A 0.01A 0~200A : ±1.2% rdg ± 5dgt
200~250A : ±3.0% rdg ± 5dgt
250~300A : ±5.0% rdg ± 5dgt
U type CT
Range : AC 300A
Max.size of conductor : 20mmφ
Accuracy : 23℃±5℃ 80%RH or less (50/60Hz)
Cable type Resolution Accuracy
Single phase IV cable 0.1A Approx. ±5%
Parallel VVF cable 0.1A Approx. ±5%
Three phase VVR cable 0.1A Approximate value