Multi Measuring Instruments Co.,Ltd. Japanese Chinese
Google
 

AC clamp leaker

Digital Clamp Tester with 80mmφ CT

PRODUCTS
AC Leakage Current, 200mA/2A/20A /200A/1000A, 80mmφ CT
Model MCL-800D
Digital Clamp Leaker. Model MCL-800D
FEATURES
  • 80mmφCT window and wide current measurements from 0.1mA to 1000A.
  • DCmV analog data output for recorder.
  • Least affection from the external magnetic field.
Show detail Catalog PDF
DETAIL
SPEC
SPECIFICATIONS
Measuring method : Dual slope integration mode
Display : 3.5 digit LCD, max. reading of 1999
Accuracy : 23℃±5℃ 80%RH or less (50/60Hz)
Range Resolution Accuracy
AC 200mA 0.1mA ±2.0% rdg ± 5 dgt
AC 2A 1mA
AC 20A 10mA
AC 200A 0.1A
AC 1000A 1A
Jaw opening capability : 80mmφ
Over range indication : Blanking of all digits except MSD 1
Low battery indication : "B" mark on LCD
Data hold indication : "H・D" mark on LCD
Sampling : 2 times/sec
Sampling : 2 times/sec
Data output : DC100mV (for full scale)
Limitation of circuit voltage : Less than AC 600V
Withstanding voltage : AC 2000V 1 minute max. (Between the core of CT and outer case)
Operating temperature : 0℃ to 40℃, 80%RH max. ( Without condensation )
Storage temperature : -10℃ to 60℃, 70%RH max. ( Without condensation )
Power supply : 1.5V (AM-4, LR03 or AAA)×2
Power consumption : 3 mW
Battery life : Approx. 350 hours ( Alkaline batteries )
Size : 138(W)×225(H)×37(D)mm
Weight : Approx. 500g
Accessories :
Hard carrying case : 1
Instruction manual : 1
Batteries : 2